Permit Number:
F19-1252
Permit Type:
Commercial Trade Permit - Alteration Fire
Address:
700 G ST Anchorage
Location:
Work Description:
FIRE ALARM WITH 100 DEVICES - SIL
CHILD OF C19-2324
Status:
Closed
Project Name:
CHILD OF C19-2324
Review Type:
Fire System
Result:
Correction
Result Date:
1/2/2020 3:25:00 PM
Comments:
Code Section
Review Comment
Status
1
_
Building is equipped with a smoke control system and all detection and control system wire is required to be installed on continuous raceway per the requirements of the 2012 IFC 909.12.1.
2
_
The following rooms do not have wall to wall strobe coverage per the requirements of 2010 NFPA 72"
Room 480 - increase to 75 cd.
Room 476 - increase to 75 cd
Room 468 - increase to 30 cd
Room 439 - increase to 30 cd
Room 430 - increase the 30 to 95 cd
3
_
Show on plans that the 120 volt electrical power is being supplied by the emergency circuits per the requirement of 2012 IFC 604.2.15.2
4
_
Missing multiple floors that are part of the scope of work.
Advisory Information: