INTERIOR FINISH UPGRADES TO INCLUDE NEW KITCHEN CASEWOR, FINISHES, APPLIANCES AND FIXTURES. BATHROOMS TO RECIEVE NEW FLOORING, SHOWER SURROUNDS, CASEWORK AND SUSTAINABLE LIGHTING RETROFIT IN KITCHEN AND BATH. -CONTRACTOR TO PAY INSPECTIONS AE
Reviewed by: Bergstrom, Leigh W.
Phone: 343-8326
Fax: 249-7615
Email: BergstromLW@muni.org
Permit Manager: Andrew Earp
Phone: 343-8338
Email: Earpal@muni.org
Project: UAA MAC HOUSING RENOVATION BLDG 1
Review Number: 442319
1) STATUS: 12-12-2019 Comments to be addressed. 12-26-2019 APPROVED.
2) The following comments based upon the 2012 International Building Code (IBC) must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC or any federal, state or local regulations. RESOLVED 12-26-2019.
3) G001 It appears that the construction is either Type "V-A" or "V-B" and not "III-B" requiring 2-hour exterior walls. RESOLVED PER RE-SUBMITTAL RECEIVED 12-17-2019.
4) G001 The occupancy Type is "R-2" for dormitories and not "B" for business. RESOLVED PER RE-SUBMITTAL RECEIVED 12-17-2019.
5) 01 & 03/A102 & 02/A412 The shower head and controls for a transfer-type shower mount on the opposite side of the compartment from the seat and not behind the seat, per ICC/ANSI A117.1-608.2.1.3. RESOLVED PER RE-SUBMITTAL RECEIVED 12-17-2019.
6) 02/A412 Elevation 2 Grab bars do not mount on the wall behind the shower seat. (ICC/ANSI A117.1-608.2.1) RESOLVED PER RE-SUBMITTAL RECEIVED 12-17-2019.
7) 01/A412 The location of the stove top controls shall require reaching across the burners. (ICC/ANSI A117.1-804.5.4.3) RESOLVED PER RE-SUBMITTAL RECEIVED 12-17-2019.
8) 02/A412 Elevation #3 The water closet clear space is 5'-0" as shown on 01/A102. (ICC/ANSI A117.1-604.3.1) RESOLVED PER RE-SUBMITTAL RECEIVED 12-17-2019.
9) 02/A412 Elevation #3 The water closet flush control shall be located on the open side of the fixture. (ICC/ANSI A117.1-604.6) RESOLVED PER RE-SUBMITTAL RECEIVED 12-17-2019.
10) When the above comments have been addressed, please update the plans at the MOA Plans Review Office with three sets of revised architectural pages to include clouded changes, engineers stamp and signature. RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT. (23.10.104.8.1) RESOLVED 12-26-2019.