Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C19-2400
Permit Type: Commercial Building Permit - None BldgAlter
Address: 4951 BUSINESS PARK BLVD Anchorage
Location:
Work Description: CHANGE AN EMPLOYEE LOCKER ROOM INTO A ROOM FOR TWO DENTAL X-RAY MACHINES - MJD
Status: Issued
Project Name: ANHC X-RAY ROOM
Review Type: Electrical
Result: Approved
Result Date: 12/13/2019 3:21:00 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Electrical Plan Review Status:

The electrical plans has been reviewed and approved.

------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------

Electrical Comments

 

Reviewed by: David Abuobaid                                                 Permit #: C19-2400

Phone: 343-8333                                                                      Date: 12/13/2019        

Fax:     249-7775                                                                      

Email:  AbuobaidDH@muni.org

Permit Manager: Melissa Davidson

Phone: 343-8339

Email:  Pdavidsonmj@muni.org

Project: ANHC X-Ray Room (Fax: no fax #)

__________________________________________________________________________________  

REQUIREMENT OF ELECTRICAL SCOPE OF WORK:
Please provide the electrical scope of work for the generator and include wiring method, existing service load calculations, panel schedules with connected and demand loads, one-line diagram, and accessibility to 0ercurrent protection so we can determine if work requires 100% designed engineered drawing by a registered professional electrical engineer of the State of Alaska.

 