Structural Comments
Reviewed by: Hellman, Becky A. Permit #: C19-1973
Phone: 343-8237 Second Review
Fax: 249-7400 Date: 12-11-19
Email: hellmanba@muni.org
Permit Manager: Bob Parker
Phone: 343-8391
Email: Parkerrw@muni.org
Project: Alaska Hospital tract B3 – 2801 Debarr Rd – ARH Pharmacy Renovations
____________________________________________________________________________________
Plan review comments:
12-11-19 Calculations that were provided were reviewed; see the following comments below that came from the review of this project.
1. This review is a code compliance review based on the requirements of the 2012 International Residential Code (IRC), 2012 International Building Code (IBC) and all adopted references thereto as amended by the Municipality of Anchorage in the Anchorage Municipal Code (AMC) Title 23. This review does not permit the violation of the building codes, nor any federal, state, or municipal regulation.
2. Please provide general notes for materials specs, welding, etc.
3. Please verify if special inspections is required; please clarify what inspections are needed or not needed on the plan. 1705.2.2.1 and 23.15.1705.2.2.1
4. See details 4 and 5; Please fix the welding symbols. For the channel to beam weld and tube, the flare bevel weld wouldn’t have a thickness and the use of the “all around” mark would be correct.
The channel weld should be a fillet weld.
Address all comments above to complete the permit process. Please provide corresponding letter that describes how comments have been addressed and where on the plans the changes have occurred. Any additional information that is provided to address the above comments could result in additional comments based on the new information provided for review. All submittals should be sent or given to the permit manager for this project.