Permit Number: C19-1973
Permit Type: Commercial Building Permit - None BldgAlter
Address: 2801 DEBARR RD Anchorage
Location:
Work Description: PAHRMACY RENOVATION AND EXPANSION. THE WORK INCLUDES NEW COMPOUNDING HOODS, NEW AIR HANDLING UNIT, RELOCATION OF STAFF RESTROOM AND BREAKROOM, AND NEW FINISHES AND LIGHTING - BWP
Status: Closed
Project Name: ARH PHARMACY RENOVATION
Review Type: Architectural
Result: Approved
Result Date: 12/9/2019 9:00:54 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:


Reviewed by: Bergstrom, Leigh W.

Phone: 343-8326

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Bob Parker

Phone: 343-8391

Email: ParkerRW@muni.org

Project: ARH PHARMACY RENOVATIONS

Review Number: 441746


1) STATUS: 8-21-2019 Comments to be addressed.             9-09-2019 COMMENTS TO BE ADDRESSED.           12-04-2019 APPROVED.


2) The following comments based upon the 2012 International Building Code (IBC) must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC or any federal, state or local regulations.                      RESOLVED 9-09-2019.


3) Per Policy AG.39, submitted blueprint font size is required to be at least 3/32". Provide full size plans.                  RESOLVED PER RE-SUBMITTAL RECEIVED 8-29-2019.


4) A221                 The minimum corridor width for an occupancy less than 50 is 36" per IBC Table 1018.2. Door #E2337 reduces the minimum corridor width down to about 15" in violation of IBC 1005.7.1.                 RESOLVED PER RE-SUBMITTAL RECEIVED 12-04-2019.


5) A401                 The horizontal grab bar in the water closet side profile is show with a mounting height of 33"-36" AFF to the centerline but should be measured to the top of the gripping surface per ICC/ANSI A117.1-609.4.1.                       RESOLVED PER RE-SUBMITTAL RECEIVED 12-04-2019.


6) A401                  The ADA mounting height for a mirror is 40" AFF to the bottom of the reflective surface (not the bottom of the frame as depicted).                                      RESOLVED PER RE-SUBMITTAL RECEIVED 12-04-2019.


7) A701                  Side light window W1 requires safety glass per IBC 2406.4.2. Please clarify.                      RESOLVED PER RE-SUBMITTAL RECEIVED 12-04-2019.


8) A701                  Clarify that the existing exit door #E2346B has a minimum clear width of 32" in accordance with IBC 1008.1.1.    RESOLVED PER RE-SUBMITTAL RECEIVED 12-04-2019.


9) When the above comments have been addressed, please update the plans at the MOA Plans Review Office with three sets of revised architectural pages to include clouded changes, architects stamp and signature.RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH ALETTER OF RESPONSE ADDRESSING EACH COMMENT.  (23.10.104.8.1)               RESOLVED 12-04-2019.