Project: ALASKA USA 7TH FLOOR
Review Number: 441333
1) “Please provide details for the attachment/fastening of the ceiling baffles. Please also provide the weight of the ceiling system including the metal baffles. Prescriptive suspended ceiling seismic bracing provisions only apply to ceilings of 4 psf or less per ASCE 7-10. If the ceiling weight exceeds this an engineered seismic restraint design is required.” Submit to structural on a deferred submittal basis. ARCHITECTURE IS APPROVED AS OF 11-26-2019.