Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: X19-1903
Permit Type: Commercial Building Permit - ChangeOrdr Sign
Address: E 849 DIMOND BLVD Anchorage
Location:
Work Description: DRAWINGS AND CALCS FOR FREE STANDING SIGN (REVIEW FEES ALREADY PAID DURING ORIGINAL PERMIT) - MJD
Status: Closed
Project Name: Change Order of Bldg App C19-2162
Review Type: Structural
Result: Approved
Result Date: 11/6/2019 9:43:07 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

STRUCTURAL REVIEW COMMENTS


Reviewed by: David Misiuk

Phone: 343-7585

Email: david.misiuk@anchorageak.gov


Permit Manager: Bob Parker

Phone: 343-8391

Email: ParkerRW@muni.org


Permit #: X19-1903/C19-2162

Project: 849 East Dimond Blvd – Raising Cane’s Monument Sign


Date: November 6, 2019

____________________________________________________________________________________

REVIEW STATUS

10/22/2019 – Initial review complete; revisions are required.

11/04/2019 – 2nd review complete; additional submittals are required.

11/06/2019 – 3rd review complete: approved.


This review is based on the requirements of the Anchorage Municipal Code (AMC), 2012 International Building Code (IBC) and all adopted references thereto as amended by MOA. The following comments must be addressed before a permit can be issued. The approval of plans and specifications does not permit the violation of the codes, or any federal, state or local regulations.


The status of the 11/04/19 review comments are as follows:


1. The design wind speed is shown as 130 mph per ASCE 7-10 in the calculations and drawings. The correct wind speed, Vu, is 145 mph as determined from the MOA Three Second Gust Wind Zones map. Please revise.


Resolved.



2. The calculations indicate soil design values are determined from a geotechnical study; please provide the report.


Resolved.


 

3. Drawing 5 shows an HSS 6x6 support post but also states that the sign is connected to the masonry shown; please clarify the support condition.


Resolved.



4. Drawing 5 shows #6 bar @ 12" O.C. T & B; it appears that his should say "each face."


Resolved.



5. Please provide calculations and construction drawings for the masonry portion of the sign referenced in the drawings including foundation loads and connections to the footing and connection of the sign to the masonry.


Please provide by deferred submittal.



Please address each comment and include one copy of additional/revised calculations and two copies of additional/revised drawings. Please indicate the location of any additions or corrections in the response. All documents should be submitted to the permit manager as shown above.

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS