Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C19-2080
Permit Type: Commercial Building Permit - None BldgAlter
Address: 3801 OLD SEWARD HWY Anchorage
Location:
Work Description:

COMM T/I TO INCLUDE STRUCT/P/M/E - BWP

**CONTRACTOR TO PAY FOR INSPECTIONS** - CONTRACTOR PAID FOR 20 INSPECTIONS 11/18/2019 - MJD

Status: Closed
Project Name: JOANN FABRICS
Review Type: Architectural
Result: Approved
Result Date: 10/7/2019 3:34:00 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:


Reviewed by: Bergstrom, Leigh W.

Phone: 343-8326

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Bob Parker

Phone: 343-8391

Email: ParkerRW@muni.org

Project: JOANN FABRICS

Review Number: 438648


1) STATUS: 9-18-2019 Comments to be addressed.              10-07-2019 COMMENTS TO BE ADDRESSED.            10-08-2019 APPROVED.


2) The following comments based upon the 2012 International Building Code (IBC) must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC or any federal, state or local regulations.                 RESOLVED 10-07-2019.


3) A001                   The currently adopted NEC code is the 2017 version and ANSI A117.1 is the 2009 version.          RESOLVED PER RE-SUBMITTAL RECEIVED 10-02-2019.


4) A001                   As per the 2012 IBC the occupant load factor for a mercantile occupancy is 30 sf per person at grade level. This will significantly increase the overall occupant load and affects the plumbing fixture requirements. However, an "Alternate Means and Methods Request" may be submitted to request that this issue only, be reviewed under the 2018 IBC in which Table 1004.5 has the mercantile occupant load factor at 60 sf per person.             RESOLVED PER ALT. MEANS AND METHODS REQUEST RECEIVED 9-26-2019 on C/O #X19-1830.


5) A703                   Vestibule door and relite "C" also require tempered glazing per IBC 2406.4.1 and 2406.4.2.               RESOLVED PER RE-SUBMITTAL RECEIVED 10-02-2019.


6) 01/A703              The reference to section 01/A401 should read 03/A401.                RESOLVED PER RE-SUBMITTAL RECEIVED 10-02-2019.


7) A703                   Provide structural, seismic and wind load calculations plus fastening details for the storefront window system to include the structural engineers stamp and signature, for structural review on a deferred submittal basis.                 10-07-2019 UNRESOLVED. THIS ITEM WAS NOT ADDRESSED AND THERE WAS NO LETTER ADDRESSING COMMENTS IN THE RE-SUBMITTAL PACKAGE.               RESOLVED PER E-MAIL SENT 10-08-2019. THE INFORMATION WAS SUPPLIED IN THE SHELL PERMIT.


8) A703                   Clarify the exterior glazing "U" factor required per IECC Table C402.2 plus local amendment.                  10-07-2019 UNRESOLVED. THIS ITEM WAS NOT ADDRESSED AND THERE WAS NO LETTER ADDRESSING COMMENTS IN THE RE-SUBMITTAL PACKAGE.                 RESOLVED PER E-MAIL SENT 10-08-2019. THE INFORMATION WAS SUPPLIED IN THE SHELL PERMIT.
 

9) When the above comments have been addressed, please update the plans at the MOA Plans Review Office with three sets of revised architectural pages to include clouded changes, architects stamp and signature. RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.  (23.10.104.8.1)                  RESOLVED 10-08-2019.