Project: QUALITY SUITES
Review Number: 438048
1) STATUS: 9-25-2019 Comments to be addressed.
2) The following comments based upon the 2012 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations.
3) Provide structural and seismic calculations plus fastening details for MAU-1 and KH-1 to include the engineers stamp and signature for structural review on a deferred submittal basis.
4) Provide details for the grease hood requirements for 18" clearance from combustible construction and wall surface finish requirements per IMC 507.9 and the exception plus local amendment.
5) When the above comments have been addressed, please update the plans at the MOA Plans Review Office with three sets of revised mechanical pages to include clouded changes, engineers stamp and signature. RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT. (23.10.104.8.1)