Permit Type: Commercial Building Permit - None BldgAlter
Address: 2801 DEBARR RD Anchorage
Location:
Work Description:

REPLACEMENT OF CT CAMERA IN ROOM 2-146 WITH NEW CAMERA BY GE - MJD

GENERAL CONTRACTOR TO PAY FOR INSPECTIONS PRIOR TO ISSUING PERMIT

PERMIT EXPIRED AND REQUIRES PERMIT EVALUATION & REACTIVATION - RED 11/8/24

Status: Expired
Project Name: CT REPLACEMENT
Review Type: Structural
Result: Correction
Result Date: 10/3/2019 11:48:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

STRUCTURAL REVIEW COMMENTS

 

 

Reviewed by: David Misiuk                              

Phone: 343-7585                                                                     

Email: david.misiuk@anchorageak.gov

 

Permit Manager: Melissa Davidson

Phone: 343-8339

Email: davidsonMJ@muni.org

 

Permit #: C19-2105

Project: Anchorage Regional Hospital – CT Replacement, Room 2-146

 

Date: October 3, 2019

____________________________________________________________________________________

 

REVIEW STATUS

10/03/2019 – Initial review complete; revision and additional submittal documents required.

 

 

This review is based on the requirements of the Anchorage Municipal Code (AMC), 2012 International Building Code (IBC) and all adopted references thereto as amended by MOA. The following comments must be addressed before a permit can be issued. The approval of plans and specifications does not permit the violation of the codes or any federal, state or local regulations.

 

 

  1. Drawing sheet S1.0, Structural Floor Plan, shows an existing W12x6 just north and parallel to grid 19; please verify that the correct beam has been called out.

     

  2. Detail B on sheet S2.0 shows “Note: For top connection see detail “D” this sheet,” but detail D appears to show a section at the base and called out elsewhere on the plan. Please provide a top connection detail for this unit, if required.

     

  3. Detail C on sheet S2.0 indicates a W16x31 floor beam but the location of the cut mark on sheet S1.0 shows only W18x65 or W12x6 beams on the plan; please clarify.

     

  4. Please provide a letter of Special inspection that states who the owner will retain to perform the Special Inspections specified on sheet S1.0. [IBC 1704.2]

     

  5. It appears that structural calculations were not provided at the time of project submittal; please provide for review.

     

 

 

Please address each comment and include one copy of additional/revised calculations and two copies of additional/revised drawings. Please indicate the location of any additions or corrections in the response. All documents should be submitted to the permit manager as shown above.