Project: ARH PHARMACY RENOVATIONS
Review Number: 436455
1) STATUS: 8-21-2019 Comments to be addressed. 9-09-2019 COMMENTS TO BE ADDRESSED.
2) The following comments based upon the 2012 International Building Code (IBC) must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC or any federal, state or local regulations. RESOLVED 9-09-2019.
3) Per Policy AG.39, submitted blueprint font size is required to be at least 3/32". Provide full size plans. RESOLVED PER RE-SUBMITTAL RECEIVED 8-29-2019.
4) A221 The minimum corridor width for an occupancy less than 50 is 36" per IBC Table 1018.2. Door #E2337 reduces the minimum corridor width down to about 15" in violation of IBC 1005.7.1.
5) A401 The horizontal grab bar in the water closet side profile is show with a mounting height of 33"-36" AFF to the centerline but should be measured to the top of the gripping surface per ICC/ANSI A117.1-609.4.1.
6) A401 The ADA mounting height for a mirror is 40" AFF to the bottom of the reflective surface (not the bottom of the frame as depicted).
7) A701 Side light window W1 requires safety glass per IBC 2406.4.2. Please clarify.
8) A701 Clarify that the existing exit door #E2346B has a minimum clear width of 32" in accordance with IBC 1008.1.1.
9) When the above comments have been addressed, please update the plans at the MOA Plans Review Office with three sets of revised architectural pages to include clouded changes, architects stamp and signature.RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH ALETTER OF RESPONSE ADDRESSING EACH COMMENT. (23.10.104.8.1)