Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: F19-1155
Permit Type: Commercial Trade Permit - Addition Fire
Address: W 701 8TH AVE Anchorage
Location:
Work Description: FIRE ALARM - 77 DEVICES - RED
Status: Closed
Project Name: CONOCO PHILLIPS
Review Type: Fire System
Result: Approved
Result Date: 8/28/2019 7:12:00 AM

Comments:

 Code SectionReview CommentStatus
1_Resolved
Strobe coverage is incomplete in the following areas on the 11th floor:  Open work area 1101, Copy/Work 1157, Open work 1109, Elevator lobby 1100. 

2_Resolved
Smoke detection is incomplete in the following are of the 11th floor:  Open work 1101

3_Resolved
Strobe coverage is incomplete in the following areas on the 12th floor:  Copy/Work 1225

4_Resolved
Smoke detection is incomplete in the following are of the 12th floor:  Hall 1234 and Hall 1227

5_Resolved
Correct plans to show correct address of: 701 W 8th Ave.   

6_Resolved
Show on plans parent permit: C19-1425

7_Resolved
NOPR issued to Criterion General and Laker Electric for installing/modifying the fire alarm system without a permit.




Advisory Information:

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS