Result: Correction
Result Date: 8/23/2019 10:31:29 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

REQUIREMENT OF ELECTRICAL SCOPE OF WORK:
Please provide the electrical scope of work and include wiring method, existing service load calculations, panel schedules with connected and demand loads, one-line diagram, and accessibility to over-current protection so we can determine if work requires 100% designed engineered drawing by a registered professional electrical engineer of the State of Alaska. 