IMPROVEMENTS TO THE BUILDING SHELL AND SITE ELEMENTS ONLY AT TENANT SUITE A-1 UNIVERSITY CENTER - RED
NOTE: THIS PERMIT WILL BE CLOSED OUT WITH A CERTIFICATE OF COMPLETION ONLY ONCE SHELL & SITE UPGRADES ARE COMPLETE. SEPERATE PERMIT TO BE SUBMITTED AT LATER DATE FOR INTERIOR TENANT IMPROVEMENT UPGRADES
Permit #: C19-1766
Project: University Center Suite A-1
Date: 2019 July 19
____________________________________________________________________________________
PERMIT STATUS
07/19/2019 – Initial review complete. Comments issued.
1. CLIP CONECTIONS
The calculations appear to check the connection of the clips with (4) #12 screws and 1/4” diameter masonry screws. This is different than the specified connections on Sheet S201 which use (3) #14 screws and 3/8” masonry screws. Please clarify the connection design.
2. DEFERRED SUBMITTALS (NO RESPONSE REQUIRED)
The following items have been identified as deferred submittal items:
· Storefront Design
All deferred submittals must be sealed by a Professional Engineer licensed in the State of Alaska. Submittals must be reviewed for general conformance by the Registered Design Professional prior to submitting to Building Safety for review. Deferred submittals must be reviewed and approved by Building Safety prior to installation/construction.
[Reference: AMC § 23.10.104.11]