Permit Number: C19-1766
Permit Type: Commercial Building Permit - None BldgAlter
Address: 3801 OLD SEWARD HWY Anchorage
Location:
Work Description:

IMPROVEMENTS TO THE BUILDING SHELL AND SITE ELEMENTS ONLY AT TENANT SUITE A-1 UNIVERSITY CENTER - RED

NOTE: THIS PERMIT WILL BE CLOSED OUT WITH A CERTIFICATE OF COMPLETION ONLY ONCE SHELL & SITE UPGRADES ARE COMPLETE. SEPERATE PERMIT TO BE SUBMITTED AT LATER DATE FOR INTERIOR TENANT IMPROVEMENT UPGRADES

Status: Closed
Project Name: UNIVERSITY CENTER -STE A-1 SHELL & SITE IMPROVE
Review Type: Structural
Result: Correction
Result Date: 7/19/2019 2:08:02 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:


Permit #: C19-1766

Project: University Center Suite A-1

Date: 2019 July 19

____________________________________________________________________________________

 

PERMIT STATUS

07/19/2019 – Initial review complete. Comments issued.

 

 

1. CLIP CONECTIONS

The calculations appear to check the connection of the clips with (4) #12 screws and 1/4” diameter masonry screws. This is different than the specified connections on Sheet S201 which use (3) #14 screws and 3/8” masonry screws. Please clarify the connection design.

 

2. DEFERRED SUBMITTALS (NO RESPONSE REQUIRED)

The following items have been identified as deferred submittal items:

 

·       Storefront Design

 

All deferred submittals must be sealed by a Professional Engineer licensed in the State of Alaska.  Submittals must be reviewed for general conformance by the Registered Design Professional prior to submitting to Building Safety for review.  Deferred submittals must be reviewed and approved by Building Safety prior to installation/construction.

[Reference:  AMC § 23.10.104.11]