Permit Type: Commercial Building Permit - None BldgAlter
Address: 3801 OLD SEWARD HWY Anchorage
Location:
Work Description:

IMPROVEMENTS TO THE BUILDING SHELL AND SITE ELEMENTS ONLY AT TENANT SUITE A-1 UNIVERSITY CENTER - RED

NOTE: THIS PERMIT WILL BE CLOSED OUT WITH A CERTIFICATE OF COMPLETION ONLY ONCE SHELL & SITE UPGRADES ARE COMPLETE. SEPERATE PERMIT TO BE SUBMITTED AT LATER DATE FOR INTERIOR TENANT IMPROVEMENT UPGRADES

Status: Closed
Project Name: UNIVERSITY CENTER -STE A-1 SHELL & SITE IMPROVE
Review Type: Fire
Result: Correction
Result Date: 7/19/2019 7:43:08 AM

Comments:

 Code SectionReview CommentStatus
1_
STAIR RISER PROFILE
Refer to Detail 3/A401. The detail shows open risers on the exterior service entrance stair. Please justify as an exterior stair; it appears riser openings are limited to a passage of a 4 in. sphere.
Reference: IFC Section 1009.7.5.3