Register
My Neighborhood
Jobs
Contact Us
Home
Residents
Businesses
Government
Visitors
Departments
Public Safety
Transportation
Recreation
ePay
Maps
Services A-Z
Muni.org
>
Departments
>
Development Services
> Permit Information & Inspection Request
Click Here To Go Back To Permit Information
Permit Number:
C19-1573
Permit Type:
Commercial Building Permit - None BldgAlter
Address:
W 5000 INTERNATIONAL AIRPORT RD Anchorage
Location:
Work Description:
PARKING & ACCESS UPGRADES OF TED STEVENS INT. AIRPORT - RED
Status:
Expired
Project Name:
Review Type:
Private Development Site Civil Review
Result:
NA
Result Date:
6/13/2019 10:33:00 AM
Comments:
Code Section
Review Comment
Status
Advisory Information:
Non-Applicability, ASM Vol.1 Section 1.4.2. MG 6-13-19.
ADA Compliance
Privacy Statement & Disclaimer
Employee Search
eNewsletter
RSS
OFFICIAL WEB SITE OF THE MUNICIPALITY OF ANCHORAGE, ALASKA
632 West 6th Avenue, Anchorage, Alaska 99501