Permit Number:
F19-1053
Permit Type:
Commercial Trade Permit - New Fire
Address:
3801 OLD SEWARD HWY Anchorage
Location:
Work Description:
FIRE SPRINKLER - 114 HEADS - RED
Status:
Closed
Project Name:
OLD PANTRY (NATURAL PANTRY)
Review Type:
Fire System
Result:
Correction
Result Date:
5/7/2019 1:41:00 PM
Comments:
Code Section
Review Comment
Status
1
_
Provide full engineered drawing with hydraulic calculation complying with the 2012 IFC 901.2 and 2010 NFPA 13 chapter 22. Plans have no scope of work, no sprinkler head info for what is being removed and installed, one page of drawings have red dots and other set is all black and white. This is not an acceptable set of drawings for review or submittal.
2
_
Provide owners statement of use of the space to include storage arraignment
3
_
Under the 2012 IEBC section section 904 for sprinkler systems greater than 50% of the system is affected and shall be required to be seismically upgraded per section 804.2.2 item 2.