Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C19-1196
Permit Type: Commercial Building Permit - None BldgNew
Address: E 849 DIMOND BLVD Anchorage
Location:
Work Description:

NEW RESTAURANT WITH INDOOR DINING AREA, COMMERCIAL KITCHEN AND DRIVE-THRU LANE - RED

2600 SF - TYPE VB CONST / A-2 OCCUPANCY

Status: Closed
Project Name: RAISING CANE'S
Review Type: Right of Way
Result: Approved
Result Date: 5/21/2019 10:16:00 AM

Comments:

 Code SectionReview CommentStatus
1-

Advisory Comment: Right of Way Permit required for all work in Municipal Rights of Way, Public Use, generic Utility, Storm Drainage, and some BLM Easements. Types of work include, but are not limited to water and sewer service connections, new driveways, drainage improvements and landscaping improvements. Only contractors with a current Right of Way Bond on file in the Right of Way Office may obtain a Right of Way Permit.

Resolved


2-

Provide or correct the Vicinity or Location Plan.

Resolved
Show the easement on the eastern side of the property where the new water service is passing through.

3-

Provide or correct the Site or Plot Plan.


Resolved


4-

Ensure General Notes include all construction to be in accordance with current version of MASS and the DCM.

Resolved
The on property drainage piping does not follow the pattern the MOA has for the private drain system. See the attached excerpt from the MOA mapping picture.

5-

Provide civil details such as a pavement cut replacement detail, curb cut details as required, or refer in the general notes to comply with MASS details.


Resolved


6-

Show, label, and dimension all recorded or platted easements, property lines, street names, rights of way, and right of way centerlines.


Resolved
All storm drain connections where there is a change of direction or pipe size must have a structure to allow inspection and cleaning operations.

7-

Correct all easement names to that of the plat(s) of record or recorded documents.     


Resolved





Advisory Information:

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter