Register
My Neighborhood
Jobs
Contact Us
Home
Residents
Businesses
Government
Visitors
Departments
Public Safety
Transportation
Recreation
ePay
Maps
Services A-Z
Muni.org
>
Departments
>
Development Services
> Permit Information & Inspection Request
Click Here To Go Back To Permit Information
Permit Number:
F19-1053
Permit Type:
Commercial Trade Permit - New Fire
Address:
3801 OLD SEWARD HWY Anchorage
Location:
Work Description:
FIRE SPRINKLER - 114 HEADS - RED
Status:
Closed
Project Name:
OLD PANTRY (NATURAL PANTRY)
Review Type:
Fire System
Result:
Correction
Result Date:
4/16/2019 3:07:00 PM
Comments:
Code Section
Review Comment
Status
1
_
Provide full engineered drawing with hydraulic calculation complying with the 2012 IFC 901.2 and 2010 NFPA 13 chapter 22. Plans have no scope of work, no sprinkler head info for what is being removed and installed, one page of drawings have red dots and other set is all black and white. This is not an acceptable set of drawings for review or submittal.
2
_
Provide owners statement of use of the space to include storage arraignment
Advisory Information:
ADA Compliance
Privacy Statement & Disclaimer
Employee Search
eNewsletter
RSS
OFFICIAL WEB SITE OF THE MUNICIPALITY OF ANCHORAGE, ALASKA
632 West 6th Avenue, Anchorage, Alaska 99501