Permit Number: C19-1251
Permit Type: Commercial Building Permit - None BldgAlter
Address: 9138 ARLON ST Anchorage
Location:
Work Description: INTERIOR T.I. FOR NEW OFFICE SPACE WITH WALLS OVER 9FT IN HEIGHT TO INCLUDE ELECTRICAL - RED
Status: Closed
Project Name: UMV
Review Type: Electrical
Result: Correction
Result Date: 3/29/2019 10:13:01 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Electrical Comments

 

Reviewed by: David Abuobaid                                                  Permit #: C19-1251

Phone: 343-8333                                                                       Date: 3/26/2019

Fax:     249-7775                                                                       Response date: 3/30/2019

Email:   AbuobaidDH@muni.org

Permit  Manager: Richard Dienes-Oehm

Phone:  343-8034

Email:   DienesOehmRE@muni.org

Project: UMV Abbott TI (Fax: no fax provided)

____________________________________________________________________________________  
1. The following comments based on the 2014 National Electrical Code (NEC) must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the NEC or any federal, state or local regulations.

Response: no response needed

 

2.  CIRCUIT DIRECTORY OR CIRCUIT INDENTIFICATION ON FLOOR PLAN & PANEL SCHEDULES:

Sheet E1 (Panel Schedules and Floor Plans Circuit Identifications). Panel schedules have many circuits named recp lobby workstations, new washer/dryer combo, receptacle lobby counter and office, new recp break room counter. Please note that these circuits should be individually identified with their locations on floor plan and on the panel schedule according to NEC 408.4 for circuit identifications.

Response: Correction is provided on the plans. Approved

 

3. SERVICE LOAD CALCULATION:

Sheet E1 (Panel D Load Calculation). The plans show calculation “existing is 200 Amps and per panel schedule calculation is 103.5 Amps.

Please provide the calculations for feeder loads for the existing building as required by NEC Section 220.87.

Response: Correction need to be according to NEC Section 220.87. Correction

 

4.  When the above comments have been addressed, please update the electrical plans at the MOA Plans Review Office with three (3) sets of revised electrical pages to include clouded changes, electrical engineers stamp and signature.

 