Permit Number: X18-1748
Permit Type: Commercial Building Permit - ChangeOrdr BldgAlter
Address: W 325 8TH AVE Anchorage
Location:
Work Description: Remodel Lobby and Dining area to include electric - BWP
Status: Closed
Project Name: Change Order of Bldg App C17-2028
Review Type: Architectural
Result: Approved
Result Date: 3/13/2019 4:28:00 PM

Comments:

 Code SectionReview CommentStatus
1_Resolved
All "ID" series Drawings; Under the Drawing Numbers, "NOT FOR CONSTRUCTION" is indicated.  When the following comments are addressed, please provide  "100% CONSTRUCTION DRAWINGS" for your resubmittal.

2_Resolved
Please provide a Door Schedule that identifies all new door types, sizes, and hardware.  There was no response to this comment.  Please verify that there are no door changes or provide a Door Schedule that identifies all new door types, sizes, and hardware.

3_Resolved
Please provide your new partition construction details including cross sections, materials, height, and attachment details.  Some of this was provided; however, it was not clear for all new walls. Please clarify.

4_Resolved
Please show all existing and revised/new Exit Signs and Emergency Lighting on either the Architectural Drawings or the Electrical Drawings (or both).  Exit Signs were shown on the FP drawings and Emergency Lighting were shown on the Electrical Drawings.

5_Resolved
Please show existing and revised/new Fire Extinguisher locations, types, and sizes.  Fire Extinguisher locations were shown on the FP drawings.  Fire Extinguisher types and sizes will become a Fire Inspection item..

6_Resolved
The plans in the original submittal were redlined to show the requirements for grab bars in the ADA rooms per 2009 ICC/ANSI A117.1.  As a minimum, the 18 inch vertical grab bar in the ADA toilet rooms are not shown on the plans and it is not clear whether all the required grab bars are included in the ADA shower enclosures.   Note that the same ID plans were resubmitted without incorporating these redlined requirements.  Please verify compliance with the ADA requirements in the 2009 ICC/ANSI A117.1. 