Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C19-1196
Permit Type: Commercial Building Permit - None BldgNew
Address: E 849 DIMOND BLVD Anchorage
Location:
Work Description:

NEW RESTAURANT WITH INDOOR DINING AREA, COMMERCIAL KITCHEN AND DRIVE-THRU LANE - RED

2600 SF - TYPE VB CONST / A-2 OCCUPANCY

Status: Closed
Project Name: RAISING CANE'S
Review Type: Architectural
Result: Correction
Result Date: 4/2/2019 9:57:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Architectural Comments

 

Reviewed by: David Abuobaid                                                 Permit #: C19-1196

Phone: 343-8333                                                                      Date: 4/1/2019

Fax:     249-7775                                                                      

Email:   AbuobaidDH@muni.org

Permit  Manager: Richard Dienes-Oehm

Phone:  343-8034

Email:   DienesOehmRE@muni.org

Project: Raising Canes (Fax: no fax provided)

____________________________________________________________________________________  
1.  The following comments based upon the 2012 International Building Code (IBC) must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC or any federal, state or local regulations. 

 

2.  EXIT THRU TRASH STAGING AREA:

Sheet G003. Please verify that the exit path remain open. Provide on the plan the layout that ensure the exit path will remain open. 

 

3.  CODE ANALYSIS (AREA AND HEIGHT):

Sheet G-003. (Occupant Load). It the stated in the code study that the total area allowed is 28,500. Do you mean 10,500?

 

4.  EXHAUST HOOD:

Sheet A101. In the mechanical section, it state that the exhaust hood in the architectural plans. Please show the exhaust hood details in the architectural plans.  

 

5.  WALK-IN COOLERS AND FREESERS

Sheets A101 (Walk-in Cooler and Freezer). Please verify that the cooler wall constructions comply with thermal barrier requirement stated in IBC Section 2603.4.1.3.

 

6.  DOOR HARDWERE:

Sheets A102 and A601. Please verify that doors # 101, 103, 103A, 142, 142A are provided with panic hardware. 

 

7. When the above comments have been addressed, please update the plans at the MOA Plans Review Office with three sets of revised architectural pages to include clouded changes, engineers stamp and signature. 

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter