Permit Type: Commercial Building Permit - ChangeOrdr BldgAlter
Address: W 325 8TH AVE Anchorage
Location:
Work Description: Remodel Lobby and Dining area to include electric - BWP
Status: Closed
Project Name: Change Order of Bldg App C17-2028
Review Type: Mechanical
Result: Approved
Result Date: 3/6/2019 10:40:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:


Bergstrom, Leigh W.

Phone: 343-8326

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Bob Parker

Phone: 343-8391

Email: ParkerRW@muni.org

Project: QUALITY SUITES #C17-2028

Review Number: 424548


1) STATUS: 10-23-2018 Comments to be addressed.                2-20-2019 COMMENTS TO BE ADDRESSED.                3-06-2019 APPROVED.


2) The following comments based upon the 2012 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations.                  RESOLVED 2-20-2019.


3) Provide mechanical plans that are signed and sealed by an Alaska registered professional mechanical engineer.            RESOLVED PER RE-SUBMITTAL RECEIVED 2-12-2019.


4) Provide structural and seismic calculations plus fastening details for AHU-1 to include the engineers stamp and signature, for structural review on a deferred submittal basis.          RESOLVED 3-06-2019.


5) The duct penetration and air transfer opening through the wall at column line 22 require smoke dampers per IBC 509.4.2 & 717.5.5 concerning laundry rooms over 100 square feet.           RESOLVED PER RE-SUBMITTAL RECEIVED 2-25-2019.


6) When the above comments have been addressed, please update the plans at the MOA Plans Review Office with three sets of revised mechanical pages to include clouded changes, engineers stamp and signature.RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH ALETTER OF RESPONSE ADDRESSING EACH COMMENT.  (23.10.104.8.1)                     RESOLVED 3-06-2019.