My Neighborhood
Contact Us
Muni.org
>
Departments
>
Development Services
> Permit Information & Inspection Request
Click Here To Go Back To Permit Information
Permit Number:
F19-1014
Permit Type:
Commercial Trade Permit - Alteration Fire
Address:
W 325 8TH AVE Anchorage
Location:
Work Description:
Comm T/I to include P/M/E - BWP
(485) DEVICES
Status:
Closed
Project Name:
Child of Bldg C17-2028
Review Type:
Fire System
Result:
Correction
Result Date:
3/4/2019 3:01:00 PM
Comments:
Code Section
Review Comment
Status
1
_
Transfer
Fire alarm drawings are not NFPA 72 compliant after quick counter review. Ian is sending them back for redesign.
2
_
Transfer
Show on Matrix: Elevator recall primary, Elevator recall secondary, Red Hat activation, smoke detector at top of shaft to send elevator to the primary landing. Smoke detector in the machine room should send elevator to floor other than the level that the machine room is on.
3
_
Resolved
Is there duct detection in the building? If so show on plans and matrix
4
_
Resolved
Is there fire smoke dampers in the building? If so show on plans and matrix
5
_
Transfer
Show on plans ceiling heights as required by 2012 IBC section 907.1.2 #11. There are notes on the plans that indicate ceiling heights but there should be a cross section of each floor.
6
_
Resolved
Room 128 needs strobe
Elevator lobby by room 322 needs strobe
2012 IBC 907.5.2.3.1
7
_
Resolved
Rooms 148, 150, 152 require 177 cd strobes per 2010 NFPA 72 section 18.5.4.6.2
8
_
Resolved
Stair 256 where does the door go on 2nd floor? Outside to a drop to ground?
9
_
Resolved
Stair 300 and 356 required smoke detection per 2012 IBC 907.2.8.2
10
_
Resolved
Calcs do not show any amperage draw for door holders, show in calcs
11
_
Transfer
Calcs do not show the 177/110 cd strobes, show in calcs. The one lines do not reflect the calcs and the calcs are off and not the correct ones for the devices listed.
12
_
Transfer
With voltage drop calculations starting at 20.4 volts and ending voltage of 16 volts as listed on the plans, the amperage listed for the devices are for 24 vdc. Use UL max amperage or 16vdc amperage for device in calculations.
Starting Voltage of 20.4 dc required per 2010 NFPA 72 section 10.14.1
13
_
Transfer
Dedicated Branch Circuit required per the 2010 NFPA 72 section 10.5.5.1 for 120 VAC to panels, show on plans.
14
_
Resolved
What gas detection is in the hotel?
Reference Flag note 1 on FA1.1
15
_
Resolved
Show on plans for dry sprinkler system monitoring of the sprinkler tamper, water alarm , low air.
Show on Matrix sprinkler operation
Reference Flag note 2 on FA1.1
16
_
Resolved
Update wiring for initiating devices to 16/2 for what the electrical contractor is installing
17
_
Resolved
Room 138, provide smoke detection over fire alarm panels 2012 IBC 907.4.1
18
_
Resolved
Show on matrix operation of the elevator damper.
19
_
Resolved
Plan review stopped, provide code compliant plans in accordance with the 2012 IBC, 2010 NFPA 72 and MOA ammendments. There are still items to be addressed however this is a complete list.
20
_
Low frequency sounder bases have the wrong calcs. Calcs should start at 16 VDC.
21
_
A pull station will be required at the electric room 122.
22
_
Show a smoke or heat detector at the annunciator in the entry.
Advisory Information:
ADA Compliance
Privacy Statement & Disclaimer
Employee Search
eNewsletter
OFFICIAL WEB SITE OF THE MUNICIPALITY OF ANCHORAGE, ALASKA
632 West 6th Avenue, Anchorage, Alaska 99501