Comments:
Code Section
Review Comment
Status
1
_
Resolved
(1) Provide the hardware type for doors 227, 228, and the door between hall 3228 and waiting 2327 to confirm that the hardware function will allow full single action egress.
(2) Provide an e-light in the hall between doors 228 and 228A.
(3) Have a note that the general contractor will have the fire alarm devices and sprinkler system upgraded due to wall change to meet the code upon completion of the job with appropriate permits if required.
Advisory Information: