Permit Number:
F19-1014
Permit Type:
Commercial Trade Permit - Alteration Fire
Address:
W 325 8TH AVE Anchorage
Location:
Work Description:
Comm T/I to include P/M/E - BWP
(485) DEVICES
Status:
Closed
Project Name:
Child of Bldg C17-2028
Review Type:
Fire System
Result:
Correction
Result Date:
2/5/2019 8:44:00 AM
Comments:
Code Section
Review Comment
Status
1
_
Fire alarm drawings are not NFPA 72 compliant after quick counter review. Ian is sending them back for redesign.
2
_
Show on Matrix: Elevator recall primary, Elevator recall secondary, Red Hat activation
3
_
Is there duct detection in the building? If so show on plans and matrix
4
_
Is there fire smoke dampers in the building? If so show on plans and matrix
5
_
Show on plans ceiling heights as required by 2012 IBC section 907.1.2 #11
6
_
Room 128 needs strobe
Elevator lobby by room 322 needs strobe
2012 IBC 907.5.2.3.1
7
_
Rooms 148, 150, 152 require 177 cd strobes per 2010 NFPA 72 section 18.5.4.6.2
8
_
Stair 256 where does the door go on 2nd floor? Outside to a drop to ground?
9
_
Stair 300 and 356 required smoke detection per 2012 IBC 907.2.8.2
10
_
Calcs do not show any amperage draw for door holders, show in calcs
11
_
Calcs do not show the 177/110 cd strobes, show in calcs.
12
_
With voltage drop calculations starting at 20.4 volts and ending voltage of 16 volts as listed on the plans, the amperage listed for the devices are for 24 vdc. Use UL max amperage or 16vdc amperage for device in calculations.
Starting Voltage of 20.4 dc required per 2010 NFPA 72 section 10.14.1
13
_
Dedicated Branch Circuit required per the 2010 NFPA 72 section 10.5.5.1 for 120 VAC to panels, show on plans.
14
_
What gas detection is in the hotel?
Reference Flag note 1 on FA1.1
15
_
Show on plans for dry sprinkler system monitoring of the sprinkler tamper, water alarm , low air.
Show on Matrix sprinkler operation
Reference Flag note 2 on FA1.1
16
_
Update wiring for initiating devices to 16/2 for what the electrical contractor is installing
17
_
Room 138, provide smoke detection over fire alarm panels 2012 IBC 907.4.1
18
_
Show on matrix operation of the elevator damper.
19
_
Plan review stopped, provide code compliant plans in accordance with the 2012 IBC, 2010 NFPA 72 and MOA ammendments.