Permit Number: C19-1055
Permit Type: Commercial Building Permit - None BldgAlter
Address: 2801 DEBARR RD Anchorage
Location:
Work Description: REMODEL OF ARH SENIOR CLINIC TO INCLUDE MECHANICAL AND ELECTRICAL - SIL
Status: Closed
Project Name: ARH SENIOR CLINC
Review Type: Architectural
Result: Approved
Result Date: 2/4/2019 5:33:00 PM

Comments:

 Code SectionReview CommentStatus
1_Resolved
Drawing A020, Code Synopsis; Verify that this TI is being performed as an 2012 IEBC Level 2 Alteration.

2_Resolved
Drawing A021, Vertical Assembly Types; Interior Partition Type E indicates a 2 hour assembly with existing wood framing.  How is this possible in a non-combustible Building Type IIB?  I could not find where Interior Partition Type E is called out on the plans; please clarify.

3_Resolved
Drawing A701, Door and Frame Schedule; Door 208 does not have any data indicated on the Door and Frame Schedule.  I assume that Door 208 has identical data as indicated for Doors 202, 203, 204, and 205.   Please verify.

4_Resolved
Drawing A701, Door and Frame Schedule;  Doors 202, 203, 204, 205, 208, 215A, and 222 are indicated indicated as existing 32" on the Door and Frame Schedule.  I am not sure how office and toilet doors opening into a corridor could have been code compliant when the building was built.  Please clarify.

5_Resolved
Drawing A402, Interior Elevations; Break Room - N is shown on detail 2; however, this detail does not verify that the reinstallation of the Break Room - N sink will be in compliance with the accessibility requirement for a maximum of 34" AFF to the Sink Flood Rim.  This detail references Mechanical; however, the M sheets also do not indicate compliance with the accessibility requirement for a maximum of 34" AFF to the Sink Flood Rim.. 