Register
My Neighborhood
Jobs
Contact Us
Home
Residents
Businesses
Government
Visitors
Departments
Public Safety
Transportation
Recreation
ePay
Maps
Services A-Z
Muni.org
>
Departments
>
Development Services
> Permit Information & Inspection Request
Click Here To Go Back To Permit Information
Permit Number:
C19-1055
Permit Type:
Commercial Building Permit - None BldgAlter
Address:
2801 DEBARR RD Anchorage
Location:
Work Description:
REMODEL OF ARH SENIOR CLINIC TO INCLUDE MECHANICAL AND ELECTRICAL - SIL
Status:
Closed
Project Name:
ARH SENIOR CLINC
Review Type:
Fire
Result:
Correction
Result Date:
1/28/2019 3:53:30 PM
Comments:
Code Section
Review Comment
Status
1
_
(1) Provide the hardware type for doors 227, 228, and the door between hall 3228 and waiting 2327 to confirm that the hardware function will allow full single action egress.
(2) Provide an e-light in the hall between doors 228 and 228A.
(3) Have a note that the general contractor will have the fire alarm devices and sprinkler system upgraded due to wall change to meet the code upon completion of the job with appropriate permits if required.
Advisory Information:
ADA Compliance
Privacy Statement & Disclaimer
Employee Search
eNewsletter
RSS
OFFICIAL WEB SITE OF THE MUNICIPALITY OF ANCHORAGE, ALASKA
632 West 6th Avenue, Anchorage, Alaska 99501