Permit Number:
E19-1015
Permit Type:
Commercial Trade Permit - Alteration Electrical
Address:
700 G ST Anchorage
Location:
Work Description:
INSTALL A NEW UPS SYSTEM. AE
Status:
Issued
Project Name:
CONOCOPHILLIPS ATO TOWER UPS REVISIONS
Review Type:
Fire
Result:
Correction
Result Date:
1/24/2019 12:32:06 PM
Comments:
Code Section
Review Comment
Status
Advisory Information:
Please provide information regarding the battery cabinets, the type of battery (e.g. flooded lead acid, VRLA, lithium ion, etc.) and the total quantity of material/electrolyte. If over quantities stated in IFC Section 608, please provide all documentation showing requirements of IFC Table 608.1 have been satisfied.
Reference: IFC Section 608.1