Permit Type: Commercial Trade Permit - Alteration Fire
Address: E 1713 64TH AVE Anchorage
Location:
Work Description:

Work to include Architectural, Structural, Fire, Electrical, Plumbing, and Mechanical.

S-1 : 18360 sqft - AJC  REASSIGNED TO ANDREW 11/16/16

(185) DEVICES

Status: Closed
Project Name: Child of C16-2005
Review Type: Fire System
Result: Approved
Result Date: 12/31/2018 1:28:00 PM

Comments:

 Code SectionReview CommentStatus
1_Resolved
(1) Provide intermediate branch line bracing on all branch lines. (2) Show FDC on the southwest corner of the building. (3) Show intermediate temp heads as required by the heaters. (3) Seismic bracing is not adequate. Show seismic bracing calcs and show on the plans.