Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C18-2380
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 900 5TH AVE Anchorage
Location:
Work Description:

TENANT IMPROVEMENT FOR INTERIOR OFFICE SPACE RECONFIGURATION TO INCLUDE ELECTRICAL REVIEW - RED

PLUMB/MECH TO BE SUBMITTED LATER

Status: Closed
Project Name: STATE OF ALASKA - PUBLIC ADVOCACY
Review Type: Fire
Result: Correction
Result Date: 12/31/2018 1:25:22 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

1) Exit sign just North of office 619 depicts exiting in the wrong direction (towards the new in-fill wall). Please note correct direction, or possibly it could be deleted altogether. 2) Horn strobe required in room 709 for notification. 3) 7th floor Reflected Ceiling Plan (pg. A-5) does not show required emergency egress lighting within the suite. I understand this is a minor upgrade to the suite so it may not be your SOP to include that layer in your submittal. Please advise of lighting condition and/or any projected changes. 4) As a general note, page A6 should be labeled "Floor 6 Reflected Ceiling Plan". It is currently labeled as floor 7. Everything else looks good! Thank you.