Permit Number:
F18-1098
Permit Type:
Commercial Trade Permit - Addition Fire
Address:
E 800 DIMOND BLVD Anchorage
Location:
Work Description:
FIRE ALARM - 35 DEVICES - RED
Status:
Issued
Project Name:
DIMOND CENTER TOWER
Review Type:
Fire System
Result:
Approved
Result Date:
11/7/2018 2:16:00 PM
Comments:
Code Section
Review Comment
Status
1
_
Resolved
Fire alarm system requires a full ADA upgraded per 2012 IFC section 907.5.2.3 exception 1 and MOA Local amendments to the IFC 23.45.907.5.2.3. Show complete plans for the system that it has compliant ADA strobe coverage or show on plans additional ADA strobes to bring the building into compliance with 2012 IFC 907.5.2.3 and 907.5.2.3.1
2
AMC 23.10.104.9
Deferral of any submitted items shall have the prior approval of the building official. The registered design professional in responsible charge shall list the deferred submittals on the construction documents for review.
ADA Timeline Agreement for completion 11/10/2018 Replace XLS1000 to XLS3000 2/28/2019 Phase 1 Drawing submitted to AFD for ADA compliance 11/10/2020 Phase 2 Upgrade Lower level and Mezzanine 11/10/2021 Phase 3 Upgrade First and Second Levels 11/20/2022 Phase 4 Upgrade Thrid and Fourth Levels 11/20/2023 Phase 5 Upgrade Fifth and Sixth Levels 11/10/2023 All spaces shall be ADA complinant by deadline date 11/10/2023 of occupancy of tenant spaces change within the timeline, full ADA requirements shall be met during the change of occupancy for the space changed.