Permit Number: X18-1866
Permit Type: Commercial Building Permit - ChangeOrdr BldgAlter
Address: W 325 8TH AVE Anchorage
Location:
Work Description: CHANGE ORDER TO ARCHITECTURAL AND FIRE: EXTERIOR CHANGE IN THE ROOF PORT COCHERE ENTRY OFF THE BUILDING - MJD
Status: Closed
Project Name: Change Order of Bldg App C17-2028
Review Type: Fire
Result: Approved
Result Date: 11/8/2018 11:17:31 AM

Comments:

 Code SectionReview CommentStatus
1_Resolved

The addition of the porte cochere is altering the overall footprint of the perimeter of the building. Please provide a plan showing the fire apparatus access, and that all points on the perimeter of the building are within 150 ft. of the fire lanes.

Reference: IFC Section 503.1.1

11/8/18 - Resolved. Updated plans show existing entry footprint; no significant change to fire apparatus access // PANILO


2_Resolved

Structural plans and details were not provided. Please submit for review; the roof construction materials may affect whether sprinkler protection is required to be extended below the porte cochere.

Reference: IFC Section 105.4.2, 903.3.1.2

11/8/18 - Resolved. Updated information provided; no sprinkler protection is required to be extended to this area as it qualifies as limited combustible under NFPA 13 // PANILO