The addition of the porte cochere is altering the overall footprint of the perimeter of the building. Please provide a plan showing the fire apparatus access, and that all points on the perimeter of the building are within 150 ft. of the fire lanes.
Structural plans and details were not provided. Please submit for review; the roof construction materials may affect whether sprinkler protection is required to be extended below the porte cochere.