Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: X18-1866
Permit Type: Commercial Building Permit - ChangeOrdr BldgAlter
Address: W 325 8TH AVE Anchorage
Location:
Work Description: CHANGE ORDER TO ARCHITECTURAL AND FIRE: EXTERIOR CHANGE IN THE ROOF PORT COCHERE ENTRY OFF THE BUILDING - MJD
Status: Closed
Project Name: Change Order of Bldg App C17-2028
Review Type: Architectural
Result: Correction
Result Date: 10/25/2018 3:35:00 PM

Comments:

 Code SectionReview CommentStatus
1_
Drawing G02, Code Analysis; Construction Type VB is indicated in two locations on this drawing.  I believe that since a NFPA 13R sprinkler system is installed, the allowable area for Construction Type VB is exceeded.  The Construction Type VA is likely appropriate for this building.

2_
Drawing A01, Canopy Plan and Roof Plan, Drawing A02, Elevations, Drawing A03, Sections, and Drawing A04, Sections; Since this is a Construction Type VA building, A one hour fire resistive roof is required.  The assembly indicated is close to qualifying for this one hour fire resistive requirement.  If a listed one hour fire resistive roof assembly is provided, the 3/4 inch plywood enclosed in the assembly is often allowed in the assembly listing when used in a Construction Type VA building.

3_
Drawing A01, Canopy Plan and Roof Plan, Drawing A02, Elevations, Drawing A03, Sections, and Drawing A04, Sections; Since this is a Construction Type VA building, one hour fire resistive columns and beams are required.  The assembly type is not indicated for these structural members that shows this one hour fire resistive requirement, although it is likely an existing condition.  If an existing listed one hour fire resistive assembly can be shown, please also indicate a qualified repair procedure for the assembly.

4_

Advisory Comment; Since mineral wool insulation is provided filling the full depth of the cavity (as presently shown on the drawing), then the canopy will likely not require sprinkler coverage with compliant Building Construction Type VA assemblies added to the plans.



5_
Note that all prior first submittal comments are considered resolved.




Advisory Information:

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter