Permit Number: X18-1748
Permit Type: Commercial Building Permit - ChangeOrdr BldgAlter
Address: W 325 8TH AVE Anchorage
Location:
Work Description: Remodel Lobby and Dining area to include electric - BWP
Status: Closed
Project Name: Change Order of Bldg App C17-2028
Review Type: Electrical
Result: Correction
Result Date: 10/22/2018 4:20:47 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:



Electrical Comments



 



Reviewed by: David Abuobaid                                                Permit
#: C17-2028 (X18-1748)



Phone: 343-8333                                                                      Date:
9/18/2018          



Fax:     249-7775
                                                                    



Email:  AbuobaidDH@muni.org                                             



Permit Manager: Melissa Davidson



Phone: 343-8339



Email:  Pdavidsonmj@muni.org



Project: Quality
Suites (Fax # no fax) 



___________________________________________________________________________________



REQUIREMENT OF ELECTRICAL SCOPE OF WORK:

The
sheets ID-400  to ID-405 show the remodel
for the lobby and dining room area. It also show electrical outlet with no
wiring method or circuit references.  



Please provide 100% designed engineered drawing
by a registered professional electrical engineer of the State of Alaska. The
design shall include existing service load calculations, panel schedules with
connected and demand loads, home run wiring with size of wires and conduit and
one-line diagram.