Electrical Comments
Reviewed by: David Abuobaid Permit#: C17-2028 (X18-1748)
Phone: 343-8333 Date:9/18/2018
Fax: 249-7775
Email: AbuobaidDH@muni.org
Permit Manager: Melissa Davidson
Phone: 343-8339
Email: Pdavidsonmj@muni.org
Project: QualitySuites (Fax # no fax)
___________________________________________________________________________________
REQUIREMENT OF ELECTRICAL SCOPE OF WORK:Thesheets ID-400 to ID-405 show the remodelfor the lobby and dining room area. It also show electrical outlet with nowiring method or circuit references.
Please provide 100% designed engineered drawingby a registered professional electrical engineer of the State of Alaska. Thedesign shall include existing service load calculations, panel schedules withconnected and demand loads, home run wiring with size of wires and conduit andone-line diagram.