Permit Number: C18-2202
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description:

T.I. OF EXISTING GCI STORE TO INCLUDE P/M/E - RED

CUSTOMER PAID PLAN REVIEWS ON 10/9/208 - RED

CONTRACTOR TO PAY FOR INSPECTIONS - RED

Status: Closed
Project Name: GCI - SUITE 118
Review Type: Architectural
Result: Correction
Result Date: 10/19/2018 12:03:26 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:



Architectural Comments



 



Reviewed by: David Abuobaid                                                Permit
#: C18-2202



Phone: 343-8333                                                                      Date: 10/18/2018



Fax:     249-7775                                                                     



Email:   AbuobaidDH@muni.org



Permit  Manager: Richard
Dienes-Oehm



Phone:
 343-8034



Email:   DienesOehmRE@muni.org



Project: GCI Dimond Center (Fax: no fax provided)



____________________________________________________________________________________  

1.   The following comments based upon the 2012
International Building Code (IBC) must be resolved before a permit is issued.
The approval of plans and specifications does not permit the violation of any
section of the IBC or any federal, state or local regulations. 



 



2.
 PROJECT DATA (GOVERNING CODE):



Sheet
A0.00. The building code is not 2012 Alaska building code (amended). The governing
building code is the International Building Code IBC 2012 Edition, and the
Municipality of Anchorage Amendments. Please correct the project data.



 



3.  PROJECT DATA (GOVERNING CODE):



Sheet
A0.00. The mechanical code is not 2012 Alaska mechanical code (amended). The
mechanical code is the International Mechanical Code 2012 Edition and the Municipality
of Anchorage Amendments. Please correct the project data.



 



4.  PROJECT DATA (GOVERNING CODE):



Sheet
A0.00. The plumbing code is not “plumbing code as adopt3ed by 8 ACC …”. The
plumbing code is the 2012 Uniform Plumbing Code and the Municipality of Anchorage
Amendments. Please correct the project data.



 



5.  PROJECT DATA (GOVERNING CODE):



Sheets
A0.00 and A0.05. The project data sheet

A0.00 shows construction type is VB and code information sheet A0.05 shows construction
type is II-B. They are both incorrect. The correct type of construction is
III-B. Please correct on the project data.



 



6.  PROJECT DATA (GOVERNING CODE):



Sheet
A0.00. The electrical code is not “electrical code as adopted by AAC 70.025 .....”
The electrical code is the National Electrical Code 2014 Edition and the Municipality
of Anchorage Amendments. Please correct the project data.



 



7.  PROJECT DATA (GOVERING CODE):



Sheet
A0.00. The accessibility code is not 2010 Americans with disability act. The accessibility
code is Accessible and Usable Buildings and Facilities ICC A117.1-2009. Please correct
the project data.



 



8.
Architectural review is incomplete bending receipt of the requested information
received. Additional comments may result from new information received.



When
the above comments have been addressed.



Please
update the plans at the MOA Plans Review Office with three sets of revised
architectural pages to include.