Permit Number: M18-1837
Permit Type: Commercial Trade Permit - Alteration Mechanical
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description: REMOVE EXISTING RTU & REPLACE W/ NEW RTU & CURB - RED
Status: Closed
Project Name: GAP INC - NEW RTU UNIT
Review Type: Mechanical
Result: Approved
Result Date: 10/16/2018 9:55:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:


Reviewed by: Bergstrom, Leigh W.

Phone: 343-8326

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Richard Dienes-Oehm

Phone: 343-8034

Email: Dienes-OehmRE@muni.org

Project: GAP INC.

Review Number: 418478



1) STATUS: 10-16-2018 Comments to be addressed.             10-24-2018 APPROVED.


2) The following comments based upon the 2012 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations.                RESOLVED 10-24-2018.


3) M-1.0 & M-1.1                        The roof penetration locations do not match between the two drawings. Please clarify.            RESOLVED PER LETTER OF RESPONSE DATED 10-22-2018.


4) M-1.1                                      Per IECC C403.2.7, all exterior ducting is to be provided with a minimum of R-8 insulation. Please clarify.                             RESOLVED PER LETTER OF RESPONSE DATED 10-22-2018.


5) When the above comments have been addressed, please update the plans at the MOA Plans Review Office with three sets of revised mechanical pages to include clouded changes, engineers stamp and signature. RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.   (23.10.104.8.1)                  RESOLVED 10-24-2018.