Permit Number: E18-2097
Permit Type: Commercial Trade Permit - Alteration Electrical
Address: 3425 TERMINAL RD Anchorage
Location:
Work Description:

PORT OFFICE TRAILER SUBMITTING FOR ELECTRICAL PERMIT TO HOOK TRAILER UP TO POWER GRID - RED

FUNDING STRING:PX.0008.2.5.009 FUND: 570800 BUS CENTER: 810000 GL ACCT: 530380

Status: Closed
Project Name: PORT OF ALASKA
Review Type: Fire
Result: Correction
Result Date: 10/13/2018 10:54:05 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Please clarify the use of the building. It appears to be a temporary office building, but is also noted as a "job trailer". If this is a job trailer as defined by AMC 23.10, please provide the permit(s) for which this trailer will be operating under. If this a general temporary building as defined by AMC 23.10, please provide plans of the trailer, site access showing fire apparatus access, and clarify water supply sources.
Reference: IFC Section 105.4.2