Permit Number: X18-1866
Permit Type: Commercial Building Permit - ChangeOrdr BldgAlter
Address: W 325 8TH AVE Anchorage
Location:
Work Description: CHANGE ORDER TO ARCHITECTURAL AND FIRE: EXTERIOR CHANGE IN THE ROOF PORT COCHERE ENTRY OFF THE BUILDING - MJD
Status: Closed
Project Name: Change Order of Bldg App C17-2028
Review Type: Fire
Result: Correction
Result Date: 10/13/2018 10:18:23 AM

Comments:

 Code SectionReview CommentStatus
1_

The addition of the porte cochere is altering the overall footprint of the perimeter of the building. Please provide a plan showing the fire apparatus access, and that all points on the perimeter of the building are within 150 ft. of the fire lanes.

Reference: IFC Section 503.1.1



2_

Structural plans and details were not provided. Please submit for review; the roof construction materials may affect whether sprinkler protection is required to be extended below the porte cochere.

Reference: IFC Section 105.4.2, 903.3.1.2