The addition of the porte cochere is altering the overall footprint of the perimeter of the building. Please provide a plan showing the fire apparatus access, and that all points on the perimeter of the building are within 150 ft. of the fire lanes.
Reference: IFC Section 503.1.1
Structural plans and details were not provided. Please submit for review; the roof construction materials may affect whether sprinkler protection is required to be extended below the porte cochere.
Reference: IFC Section 105.4.2, 903.3.1.2