Permit Number: X18-1837
Permit Type: Commercial Trade Permit - ChangeOrdr Mechanical
Address: 2801 DEBARR RD Anchorage
Location:
Work Description: Deferred to Struct - Stamped detail clarifying construction of the doghouse that encloses exhaust fan and chiller pipe connections - BWP
Status: Closed
Project Name: Change Order of M18-1468
Review Type: Structural
Result: Correction
Result Date: 10/1/2018 2:30:28 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

DEFERRED SUBMITTAL STATUS
10/1/2018 - Deferred submittal reviewed. Comments issued.

1. Please provide design of the studs. The concern is for out-of-plane wind loads and snow loads. Please note that the interior of this structure is not finished so the studs cannot be chosen from the metal stud catalog tables as these tables assumed studs are supported in the weak direction on both sides.

2. Please clarify the foundation. Is this a typical concrete stem wall with strip footing, sonotube, pile, other? Please indicate the foundation requirements on the drawings.