Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: X18-1748
Permit Type: Commercial Building Permit - ChangeOrdr BldgAlter
Address: W 325 8TH AVE Anchorage
Location:
Work Description: Remodel Lobby and Dining area to include electric - BWP
Status: Closed
Project Name: Change Order of Bldg App C17-2028
Review Type: Plumbing
Result: Correction
Result Date: 9/12/2018 4:31:37 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:


Bergstrom, Leigh W.

Phone: 343-8326

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Bob Parker

Phone: 343-8391

Email: ParkerRW@muni.org

Project: QUALITY SUITES #C17-2028

Review Number: 417166


1) STATUS: 9-12-2018 Comments to be addressed.


2) The following comments based upon the 2012 Uniform Plumbing Code must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the Uniform Plumbing Code or any federal, state or local regulations. 


3) Provide full size plumbing plans that are signed and sealed by an Alaska registered professional mechanical engineer. 


4) When the above comments have been addressed, please update the plans at the MOA Plans Review Office with three sets of revised plumbing pages to include clouded changes, engineers stamp and signature. RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.   (23.10.104.8.1)


 



ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter