Permit Number: X18-1748
Permit Type: Commercial Building Permit - ChangeOrdr BldgAlter
Address: W 325 8TH AVE Anchorage
Location:
Work Description: Remodel Lobby and Dining area to include electric - BWP
Status: Closed
Project Name: Change Order of Bldg App C17-2028
Review Type: Electrical
Result: Correction
Result Date: 9/18/2018 2:19:53 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:



Electrical Comments



 



Reviewed by: David Abuobaid                                                Permit
#: C17-2028 (X18-1748)



Phone: 343-8333                                                                      Date:
9/18/2018



Fax:     249-7775                                                                     



Email:  AbuobaidDH@muni.org



Permit Manager: Bob Parker



Phone: 343-8391



Email:  Parkerrw@muni.org



Project: Quality
Suites (Fax #: no fax)



____________________________________________________________________________________  



REQUIREMENT OF ELECTRICAL SCOPE OF WORK:



The sheets ID-400 to ID-405 shows the remodel for the
loby and dining room area. And shows electrical outlets with no wiring method
or circuit references.



Provide 100% designed engineered drawing by a
registered professional electrical engineer of the State of Alaska. The design
shall include floor plans, wiring method, home run wiring with type, size of
wires and conduits, over-current protection and existing service load
calculations, panel schedules with connected and demand loads and one-line diagram