Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: X18-1518
Permit Type: Commercial Building Permit - ChangeOrdr BldgAlter
Address: 1700 HILLCREST DR Anchorage
Location:
Work Description: DEF SUB - MECHINCAL SEISMIC RESTRAINTS - RED
Status: Closed
Project Name: Change Order of Bldg App C17-2052
Review Type: Structural
Result: Approved
Result Date: 9/17/2018 10:20:58 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

DEFERRED SUBMITTAL STATUS
7/17/2018 - Deferred submittal reviewed. Comments issued.

1. Several pieces of the equipment indicate no additional restraint required. Please justify this. Per ASCE 7-10 only equipment less than 20 lbs that are suspended from the roof or floor above is exempt from Chapter 13, and the equipment where this is noted all weigh more than this.
Comment resolved. Per discussion with Ross the response is accepted. WAB - 9/17/2018

2. Sound Attenuator S-6A make reference to a sketch that could not be located. Please indicate where in the submittal this sketch is or provide it.

Comment resolved. This detail has been provided. WAB - 9/17/2018
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS