Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C18-1851
Permit Type: Commercial Building Permit - None BldgAlter
Address: 1200 AIRPORT HEIGHTS DR Anchorage
Location:
Work Description: DEMO AND REPLACE EXISTING ENTRY GAZEBO - RED
Status: Closed
Project Name: MEDICAL OFFICE BLDG F - ENTRY GAZEBO REMODEL
Review Type: Architectural
Result: Correction
Result Date: 8/6/2018 12:00:00 PM

Comments:

 Code SectionReview CommentStatus
1_
Drawings A 302 and A 303, Wall Sections; There is P. T. plywood indicated in the wall sections.  Since the Building Code Study indicates that the Building Construction is Type IB, non bearing wood in a non combustible building must be fire resistive treated per IBC Section 603.1, item 1.

2_
Drawings A 302 and A 303, Wall Sections; There is P. T. plywood indicated in the wall sections, including in the overhead concealed space.  As stated above, since the Building Code Study indicates that the Building Construction is Type IB, non bearing wood in a non combustible building must be fire resistive treated per IBC Section 603.1, item 1.  However; for the exposed P. T. plywood in the concealed space, please also show compliance with the requirements of IBC Section 718.5.




Advisory Information:

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS