Permit Number:
F18-1109
Permit Type:
Commercial Trade Permit - New Fire
Address:
1717 TIDEWATER RD Anchorage
Location:
Work Description:
(2) ALT GAS. AE
Status:
Issued
Project Name:
MATSON- ALT GAS
Review Type:
Fire System
Result:
Approved
Result Date:
6/8/2018 1:13:00 PM
Comments:
Code Section
Review Comment
Status
1
_
Resolved
Device legend symbols do not line up with the descriptions
2
_
Resolved
What is the room wall construction and details per 2012 NFPA 2001 section 5.1.2.2 (4) (5) and (6)
3
_
Resolved
What is the required venting for each room per 2012 NFPA 2001 section 5.1.2.2 (28)
4
_
Resolved
Provide map showing location of Server room 1 and 2 at main entrance of building. Map to include location of suppression rooms, suppression panel, preaction riser location, building fire alarm system panel and sprinkler riser per AFD policy 08-003
5
_
Resolved
Fire alarm matrix indicates that suppression system will release/discharge the FM200 into both server rooms at the same time, even if there is no event in one of the server rooms. Is this correct? If not update the fire alarm matrix to indicate proper operation with one fire suppression panel controlling 2 releasing zones.
6
_
Resolved
Provide estimates positive and negative pressures from discharge per 2012 NFPA 2001 section 5.1.2.2 (10)
7
_
Resolved
Provide all items as required per 2012 NFPA 72 section 5.1.2.2 items 1 through 28 on plans
8
AMC 23.10.104.9
Deferral of any submitted items shall have the prior approval of the building official. The registered design professional in responsible charge shall list the deferred submittals on the construction documents for review.
Resolved
Items required before Final Venting calculations Installation of vents Door fan test results Installation of maps Verification of walls being able to hold pressure
9
_
Resolved
Retro Electrical permit required for the 120/220/240 volt electrical work. Anchorage Municipal Code 23.10.104.5. Reference Items D, E F (must provide panel loads to the plan review engineer)