Permit Number:
F18-1109
Permit Type:
Commercial Trade Permit - New Fire
Address:
1717 TIDEWATER RD Anchorage
Location:
Work Description:
(2) ALT GAS. AE
Status:
Issued
Project Name:
MATSON- ALT GAS
Review Type:
Fire System
Result:
Correction
Result Date:
5/30/2018 10:39:00 AM
Comments:
Code Section
Review Comment
Status
1
_
Device legend symbols do not line up with the descriptions
2
_
What is the room wall construction and details per 2012 NFPA 2001 section 5.1.2.2 (4) (5) and (6)
3
_
What is the required venting for each room per 2012 NFPA 2001 section 5.1.2.2 (28)
4
_
Provide map showing location of Server room 1 and 2 at main entrance of building. Map to include location of suppression rooms, suppression panel, preaction riser location, building fire alarm system panel and sprinkler riser per AFD policy 08-003
5
_
Fire alarm matrix indicates that suppression system will release/discharge the FM200 into both server rooms at the same time, even if there is no event in one of the server rooms. Is this correct? If not update the fire alarm matrix to indicate proper operation with one fire suppression panel controlling 2 releasing zones.
6
_
Provide estimates positive and negative pressures from discharge per 2012 NFPA 2001 section 5.1.2.2 (10)
7
_
Provide all items as required per 2012 NFPA 72 section 5.1.2.2 items 1 through 28 on plans