Permit Number:
F18-1089
Permit Type:
Commercial Trade Permit - Alteration Fire
Address:
W 5000 INTERNATIONAL AIRPORT RD Anchorage
Location:
Work Description:
FIRE ALARM WITH 2 DEVICES - MJD
CHILD OF C17-2145
Status:
Closed
Project Name:
CINNABON
Review Type:
Fire System
Result:
Approved
Result Date:
5/17/2018 10:30:00 AM
Comments:
Code Section
Review Comment
Status
1
_
Resolved
Circuit N12-21 is overloaded. Plans show 2.01 amps but actual amp draw is 3.132 amps
5 each 757-5A-SS70 15 cd plans show 0.07 amps each, spec sheet shows 0.109 amps each
2 each 757-7A-HS 15/75 cd plans show 0.09 amps each, spec sheet shows 0.150 amps each
10 each 757-3A-SS70 30 cd plans show 0.089 amps each, spec sheet shows 0.130 amps each
3 each 757-8A-SS70 110 cd plans show 0.197 amps each, spec sheet shows 0.329 amps each
2
_
Resolved
Update voltage drop and battery calculations after overload circuit is corrected
3
_
Resolved
Provide Fire Alarm Installation Affidavit
4
_
Resolved
Show floor plans that shows everything connected to BPS N12 -21/22