Permit Number:
F18-1088
Permit Type:
Commercial Trade Permit - Alteration Fire
Address:
5960 DE HAVILLAND AVE Anchorage
Location:
Work Description:
FIRE ALARM WITH 27 DEVICES - MJD
Status:
Closed
Project Name:
QUICK TURNAROUND FACILITY
Review Type:
Fire System
Result:
Approved
Result Date:
5/17/2018 9:56:00 AM
Comments:
Code Section
Review Comment
Status
1
_
Resolved
Where is this work taking place the plans show 5000 W International Airport Road, the application shows 5960 De Havilland? Update plans or application as applicable
2
_
Resolved
Provide data/install sheets for the heat detector DT-135wp
3
_
Resolved
Provide Fire Alarm Installers Affidavit
4
_
Resolved
What is the ceiling height the detectors are being mounted at?
5
_
Resolved
Provide heat detector reduced spacing when the ceiling is over 10 feet. 2010 NFPA 72 section 17.6.3.5
6
_
Resolved
Is there more building than what is being shown on the plans? Google earth show a very large building at location on plans and on application.