INTERIOR T.I. TO INCLUDE INSTALLATION OF 3 MED WORK STATIONS AND INSTALL TWO ADDITIONAL EXTERIOR DOORS - RED
P/M/E TO BE SUBMITTED LATER
Electrical Comments
Reviewed by: David Abuobaid Permit#: C18-1438
Phone: 343-8333 Date: 5/14/2018
Fax: 249-7775
Email: AbuobaidDH@muni.org
Permit Manager: Richard Dienes-Oehm
Phone: 343-8034
Email: DienesOehmRE@muni.org
Project: AnchorageNeighborhood clinic (Fax: no fax #)
____________________________________________________________________________________
REQUIREMENT OF ELECTRICAL SCOPE OF WORK:Pleaseprovide the electrical scope of work and include wiring method, existingservice load calculations, panel schedules with connected and demand loads,one-line diagram, and accessibility to 0ercurrent protection so we candetermine if work requires 100% designed engineered drawing by a registeredprofessional electrical engineer of the State of Alaska.