Permit Number:
F18-1098
Permit Type:
Commercial Trade Permit - Addition Fire
Address:
E 800 DIMOND BLVD Anchorage
Location:
Work Description:
FIRE ALARM - 35 DEVICES - RED
Status:
Issued
Project Name:
DIMOND CENTER TOWER
Review Type:
Fire System
Result:
Correction
Result Date:
5/4/2018 7:48:00 AM
Comments:
Code Section
Review Comment
Status
1
_
Fire alarm system requires a full ADA upgraded per 2012 IFC section 907.5.2.3 exception 1 and MOA Local amendments to the IFC 23.45.907.5.2.3. Show complete plans for the system that it has compliant ADA strobe coverage or show on plans additional ADA strobes to bring the building into compliance with 2012 IFC 907.5.2.3 and 907.5.2.3.1
Advisory Information:
ADA Compliance